GE MN-ValVue-v2-8-IOM Manuale di Servizio Pagina 411

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 410
411
Calibration Reset
Advanced Setup
3. Click Coupling method (Figure 238).
Figure 238 Starting Coupling
4. Pull the indexing flexure until it is centered by the pin.
ValVue 12400 displays the coupling value. The reading must be between -5% and +5%.
If the reading is beyond the limits, an adjustment is required. (Refer to the instruction for
the workshop method.)
5. Click Stop Coupling to complete.
Figure 239 Stop Coupling
Calibration Reset
The Calibration Tools window provides the ability to reset the AO Main and AO Optional to
the factory defaults.
Vedere la pagina 410
1 2 ... 406 407 408 409 410 411 412 413 414 415 416 ... 659 660

Commenti su questo manuale

Nessun commento