ValVue Digital Communications Software Ver. 2.80
376
GE Oil & Gas
Range
For an application where the level change is smaller than the displacer height, it is possible to
obtain the full signal range by adjusting the range parameters: Level LRV (Low Range Value)
and Level URV (Upper Range Value).
NOTE The SIL2 feature (see fields in red box) is available using firmware
1.1.2 or later.
Change Level LRV or URV Setting
To change the setting:
1. Enter a new value in the Level LRV or Level URV field.
2. Click Apply.
Figure 180 Changing LRV