ValVueFF Software Interface to FVP
106
GE Energy
Figure 87 Calibration Dialog Box - Range Tab
Find Range Result
The Find Range Result field displays the result of the calibration execution:
1. Isolate the valve.
2. Select the GO button to run the selected calibration.
3. Select Yes when the Stroke the Valve message box appears. Results appear in the
Find Range Result field.
Auto Stop Limits
WARNING Range Calibration strokes the valve over its entire travel.
When Auto Stop Limits is selected:
1. Isolate the valve.
2. Select the GO button.
Figure 88 Stroke Valve Message Box
Vedere la pagina 121